Wilo Stratos MAXO 50/0.5-9 -R7, Circulation Pump
Watch this product and we will notify you once it is back in stock.
Wilo Stratos MAXO 50/0.5-9 -R7, Circulation Pump
Description
Wet smart pump in single version, delivered complete with built-in motor protection, alarm output, connection 0-10 V, pump on/off, external operation indication. Equipped with permanent magnet motor, function for flow limitation and built-in frequency converter. Measurement of cooling and heating energy possible together with sensor (accessory). Energy optimization function Dynamic Adapt Plus. Together with CIF module (accessory) prepared for connection to building automation, interface CAN, LON, BACnet or Modbus.
Functions
- Heat quantity recording (with optional Wilo-media temperature sensor or analog temperature sensors, e.g. 2x PT1000 possible)
- Cooling quantity registration (with optional Wilo-media temperature sensor or analog temperature sensors, e.g. 2x PT1000 possible)
- Automatic pump shutdown when zero flow is detected (No-Flow Stop)
- Switching between heating and cooling operation (automatic, external or manual) (automatic, possible with optional Wilo-media temperature sensor)
- Adjustable flow limitation through Q-Limit function (Qmin. and Qmax.)
- Operating types twin pumps: Efficiency-optimized parallel operation for dp-c and dp-v, main/standby operation
- Save and reset the set pump settings (3 reset points)
- Error/warning message in plain text including action recommendation
- Venting function for automatic venting of the rotor chamber
- Automatic lowering operation (with optional Wilo-media temperature sensor possible)
- Automatic unblocking function and built-in full engine protection
- Dry run identification
Hydraulic Data
- Maximum operating pressure PN : 10 bar
- Call height H max: 10.7 m
- Flow Q: max 34.7 m³/h
- Minimum inlet height at 50 °C: 5 m
- Minimum inlet height at 95 °C: 12 m
- Minimum inlet height at 110 °C: 18 m
- My. medium temperature Tmin : -10 °C
- Max. medium temperature Tmax : 90 °C
- Ambient temperature min. Tmin : -10 °C
- Max. ambient temperature Tmax : 40 °C
Engine Data
- Energy efficiency index (EEI) : ≤0.17
- Mains connection : 1~230 V ±10%, 50/60 Hz
- Rated current IN : 0.2 A
- Rated current IN : 2.4 A
- Rated power P2 : 456 W
- RPM min. nmin : 650 1/min
- RPM max. nmax : 3050 1/min
- Input power (min) P1 min : 10 W
- Power consumption P1 max: 550 W
- Disturbance emission : EN 61800-3;2004+A1;2012/residential (C1)
- Interference stability : EN 61800-3;2004+A1;2012/industrial environment (C2)
- Cable gland : 5 x M16x1.5
- Insulation class: F
- Protection class: IPX4D
Specifications
- Pump housing: Cast iron
- Impeller : PPS-GF40
- Axle : 1.4028, DLC coated
- Material bearing : Carbon, antimony impregnated
- Pipe connection on the pressure side: DN 50
- Pipe connection on the suction side: DN 50
- Construction length 10: 280 mm
Measure
- Length: 420mm
- Height: 280mm
- Width: 250mm